PDF Print E-mail


Storage Tank and Pipework Leak Detection

 LAG-14ER  - Tank Interstitial Space Liquid Filled

 

 

LAG-14 Leak Control Panel


 

 

 

 

 

 

 

 


The LAG-14 ER Leak Detection System is designed to monitor the interstitial space of double skin steel or GRP non-pressurised storage tanks.   
Tanks may be located in safe or hazardous areas, above or below ground, and offset or direct fill type.   The system consists of the LAG-14 ER Leak Detector, an anti-static plastic header tank complete with electrode and LAG installation kit.   

The header tank and interstitial space is filled with a suitable leak detection liquid.    
The electrode in the header tank is normally immersed in the leak detection liquid.
A leak in either the inner or outer skin results in a fall of liquid level in the header tank, initiating a visual and audible alarm.

 Eurovac LAZ-04  - Tank Interstitial Space Vacuum Filled

EuroVac LAZ-04 Leak Detector Control Panel 

 


The Eurovac LAZ-04 Leak Detection System is designed to monitor the interstitial space of double skin steel or GRP non-pressurised storage tanks.

Tanks must be located in safe areas, either above or below ground.
A -500mbar vacuum is generated in the tank interstitial space via an internal pump.

Leaks in either the inner or outer skin results in a loss of vacuum in the tank interstitial space, initiating a visual and audible alarm.

 Europress LAD-10  - Tank Interstitial Space Pressurised

  

Europress Lad-10 Leak Detector Control Panel

 


 


The Europress LAD-10 Leak Detection System is designed to monitor the interstitial space of double skin steel or GRP non-pressurised storage tanks.

Tanks may be located in safe or hazardous areas, either above or below ground.
The tank interstitial space is pressurised via an internal pump to 510mbar.

A leak in either the inner or outer skin results in a pressure drop in the tank interstitial space, initiating a visual and audible alarm.

 LAD-R - Pipework Interstitial Space Pressurised

 

LAD-R Leak Detector Control Panel

 


 

 

Leak detector for monitoring double-skinned pipework & storage tank interstitial spaces using pressure with inert gas (Nitrogen) fill.
Single LAD-R will work with interstitial space volumes up to 1200 litres. High and low pressure audio/visual alarms.
GSM/solar options available.
The LAD- R Leak detector for monitoring double-skinned pipework & storage tank interstitial spaces using pressure with inert gas (Nitrogen) fill.

Single LAD-R will work with interstitial space volumes up to 1200 litres.

High and low pressure audio/visual alarms.

GSM/solar options available.

 

 

 PWLD - Pipework Interstitial Space Pressurised 

 

 

PWLD Leak Detector Control Panel

 


 


The PWLD Leak Detection System is specially designed to monitor the interstitial space of double skin steel or plastic  pipework.

Pipework may be located in safe or hazardous areas, either above or below ground. Low cost pressure transducers are used to monitor the pipework runs .

Trip amplifiers are set to give high and low pressure interstitial space alarms. This allows the interstitial space to have a lower working pressure than the internal pipe. For further information please contact us.

 

 

Valid XHTML and CSS.